High Voltage equipment Testing Laboratory (LAW)

Laboratory

High Voltage equipment Testing Laboratory (LAW)

The laboratory has 60 years of experience in type and design testing of power, medium and high voltage AC equipment.

about us

1
Generator 100 MVA, 10/12 kV, o mocy zwarciowej 2500 MVA
2
Generator udarowy HiVolt 1200 kV, 120 kJ
Nastawnia główna-2
Nastawnia główna

Basic laboratory equipment:

  • Three-phase short-circuit generator: rated power 100 MVA, short-circuit power 2500 MVA, rated voltage 10/12kV, frequency 50 Hz;
  • Three-phase short-circuit generator: rated power 25 MVA, short-circuit power 500 MVA (3 s), rated voltage 10/12 kV, frequency 50 Hz;
  • Three-phase power grid: 6 kV; 50 Hz, 110/6kV power transformer, 10 MVA;
  • Single-phase short-circuit transformers: rated power 3 × 33.3 MVA, short-circuit power 3 × 750 MVA (2 s), primary voltage 10 kV, secondary voltages 15/30/60/110kV;
  • High-current single-phase transformers with rated continuous power 3 × 10 MVA, symmetrical short-circuit power 41 MVA, primary voltage 10 kV, secondary voltage 250/500/1000 V, maximum short-circuit current 3s 120 kA, surge current 410 kA;
  • High-voltage test generator with truncation system capable of generating 1.2/50 μs surges with 1200 kV amplitude and 8/20 μs switching shocks with 900 kV amplitude, maximum generator energy 120 kJ;
  • 50 Hz test transformers with voltages: 300 kV, 120 kV, 80 kV, 30 kV;
  • RL RC systems for the control of power supply parameters, TRV, and modelling (simulation) of load systems.

The laboratories have various types of instruments, devices, measuring and recording equipment for low and high voltage: shunts, voltage dividers, current and voltage transformers, analogue and digital instruments, RLC bridges, oscilloscopes, specialised transient and surge recorders, multi-channel temperature recorders, optoelectronic measurement data transmission systems

The range of products tested:

  • AC switchgear in metallic enclosures for rated voltages above 1 kV up to 52 kV and in insulating enclosures for rated voltages above 1 kV up to 38 kV
  • gas-insulated switchgear with metallic enclosures for rated voltages above 52 kV
  • HV gas-insulated transmission lines with a rated voltage of 52 kV and above
  • HV to LV transformer stations
  • measuring cabinets
  • HV cables
  • AC circuit breakers
  • AC disconnectors and earth switches
  • fused disconnector switch units
  • HV fuses
  • fuse links for the protection of motor circuits
  • AC contactors
  • insulators of various types
  • transformers and chokes
  • current transformers
  • voltage transformers
  • combination transformers
  • busbars
  • surge arresters and surge protective devices
  • high and low voltage AC capacitors
  • oil-immersed and dry-type transformers
  • insulating and metallic enclosures
  • terminal boxes

insulation fittings

  • HV jumpers
  • insulating rods for voltages from 1 kV to 750 kV
  • tongs and grippers for voltages above 1 kV
  • isolation platforms
  • voltage indicators
  • hand-held tools for working at up to 1,000 VAC and 1,500 VDC
  • sleeves made of insulating material for live work
  • portable earthing devices
  • phase comparators
  • electro-insulating rubber walking mats
  • electrically insulating gloves for live work
  • Wellington boots and electrician’s boots

Tests performed

The High Voltage Switchgear Testing Laboratory performs tests, measurements and verification of the functional characteristics and properties of high voltage AC switchgear and switching gear products, as well as verification of the compliance of these products with the requirements of the relevant standards in the field of type testing and special tests, environmental tests and IP, IK protection rating, to the full extent.

The LAW laboratory performs the following tests on daily basis:

  • insulation testing with DC, AC and surge voltages in dry and rain conditions
  • testing dielectric properties
  • check of temperature increase
  • checking the making capacity of the equipment with regard to rated, switching, critical and short-circuit and overload current
  • short-time strength and n-second current tests
  • dynamic strength test with peak current
  • testing the effectiveness and short-circuit strength of protective circuits
  • testing the internal arc resistance
  • testing the time-current characteristics
  • testing the operation of triggers and relays
  • testing of fuses with lower and upper test current
  • environmental tests at various exposures
  • testing protection rating provided by enclosures (up to IP68)
  • mechanical impact test (up to IK10)
  • check of mechanical durability
  • check of air and surface insulation gaps
  • geometric measurements
  • corrosion resistance in salt spray atmosphere

Testing capabilities LAW - AB 074

Alternating current (AC)

Short-circuit current (3 phase) rms

max 120 kA

Short-circuit current (1 phase) rms

max 210 kA

Short-circuit current peak

max 400 kA

Arc protection test

max 63 kA 0.5s. 50 kA 1 s

Switching tests

max 1 = 50 k A – 7.2 kV
40 kA -12 kV
31.5 kA – 17.5 kV
16 kA – 24 kV
8 k A – 36 kV

Temperature rise

max 12 kA

Direct current (DC)

Short-circuit current

max 40 kA

Switching tests

max 80 kA dla 1 kV
max 50 kA dla 4 kV

Temperature rise

max 10 kA

Voltage tests

Mains frequency voltage

max 300 kV. 50 Hz

Lightning surge voltage 1.2/50

max 1200 kV. 120 kJ

Switching surge voltage 8/20

max 900 kV, 120 kJ

Climate chamber tests (próby A, B, Cab, Db)

Temperature range

-70oC – 180 oC

Humidity range

10% – 95% RH

IP tests

up to lP68

IK tests

Do lK1O

ACCREDITATION